Industrial burners

SELF-RECUPERATIVE AND RADIANT TUBE BURNERS : TUBE FIRING BURNERS TFB

Description:
Capacity range: 200,000 to 1,000,000 Btu/h (59 to 293 kW) Turndown: 10:1 Max. process temperature: 2200°F (1205°C) Fuel: natural gas Typical applications: tempering furnaces, hardening furnaces, reheating furnaces, fluidized bed driers, thermal oxidizers, non-ferrous melting, ladle/tundish, glass lehrs, environmental applications, preheated air Key attributes: easy set-up with built-in metering. Best high velocity burner on the market. Robust, reliable performance. Incredible efficiencies.



SELF-RECUPERATIVE AND RADIANT TUBE BURNERS : THERMJET SELF RECUPERATIVE BURNERS TJSR

Description:
Capacity range: 300,000 to 2,000,000 Btu/h (88 to 586 kW) Turndown: up to 40:1 Max. process temperature: 1900°F (1040°C) Fuels: natural gas, propane, butane Typical applications: indirect fired furnaces, tempering, hardening, continuous lines, annealing, galvanizing, liquid heating Key attributes: easy set-up with built-in orifice plates. One burner for multiple sized radiant tubes. Outstanding heat distribution.



AIR HEATING LINE-STYLE AND DUCT BURNERS : DUCT BURNERS AH-MA

Description:
Capacity: 1,200,000 Btu/h/LF (1150 kW/m) Turndown: 30:1 Max. upstream process air temperature: 450°F (232°C) Max. downstream process air temperature: 850°F (454°C) Fuels: natural gas, propane, butane Typical applications: make-up air heating, drying processes Key attributes: robust, reliable performance. Compact modular design.



AIR HEATING BURNERS : RATIOMATIC

Description:
Capacity range: 500,000 to 30,000,000 Btu/h (147 to 8785 kW) Turndown: up to 90:1 depending on burner size and chamber conditions Max. process temperature: 1900°F (1038°C) Fuels: natural gas, propane, butane Typical applications: dry-off and curing ovens, incinerators, indirect air heating, textile drying, food processing/baking, annealing, aluminium homogenizing Key attributes: easy set-up. No gas adjustment with ratio control. Robust, reliable performance.



IMMERSION TUBE BURNERS : IMMERSOJET

Description:
Capacity range: 190,000 to 8,000,000 Btu/h (56 to 2344 kW) Turndown: 7:1 minimum Max. process temperature: 200 to 400°F (93 to 204°C) Fuels: natural gas, propane, butane Typical applications: washing and rinsing of tanks, dip tanks, pickling tanks, spray washers, deep fryers, salt baths, quench tanks Key attributes: up to 80% efficiency. Allow the use of smaller, lower cost tubes.



Further ignition and monitoring components

FURTHER IGNITION AND MONITORING COMPONENTS : IGNITION TRANSFORMERS TZI, TGI

Description:
Components used in igniting and detecting burner flames including flame rods, igniters, insulators, ignition transformers and connectors



FURTHER IGNITION AND MONITORING COMPONENTS : IGNITION TRANSFORMERS TZI, TGI

Description:
Feature high ultraviolet (UV) sensitivity for monitoring gas or oil flames which cycle on and off frequently Check for a short-circuited or ""run-away"" scanner at the beginning and end of each flame cycle UL listed, CSA certified and FM approved Come with a 6-foot cable lead Safeguarded against reverse connection, the 90° UV scanner operates with 6000 Series Multi-Flame and 6500 Series controllers

Gas trains

VALVE TRAINS CONFIGURED PACKAGED VALVE : TRAINS

Description:
Rated for 110-120V / 50-60 Hz operation Designed to meet the requirements of NFPA 86 - 2003 or Industrial Risk Insurers (IRI) IM.4.2.0. The IRI version includes either a vent valve or a valve proving system Include safety shut-off valves, manual shut-off valves, high & low pressure switches, visual position indicators and pressure taps for valve seat leak testing and in-line strainers. Optional components consist of regulators, valve leak test systems, upstream and downstream gauges (2 - 1/2"" face diameter) and pilot gas trains (1/2"" or 3/8"").



VALVE TRAINS STANDARD VALVE : TRAIN SEGMENTS

Description:
Pipe sizes: 1/2 to 8 inches (25 to 200 mm). Threaded and flanged models are available depending on the pipe size specified Key attributes: faster installation, safer operation and proven reliability for global applications. Offered in the NFPA series with UL, CSA and FM approved components or in the EN 746-2 series utilizing CE-marked components.